PVC Conduit Fill Chart: Complete NEC Reference Guide

Excluding ground wires from conduit fill calculations is one of the most common code violations electricians make. Every inspector has written it up. Every experienced electrician has seen it happen. Yet the NEC is clear: equipment grounding conductors MUST be included when calculating fill.

This guide provides the complete PVC conduit fill charts you need, plus the underlying NEC rules that turn a simple table lookup into a code-compliant installation.

image 23

How Many Wires Can You Put in PVC Conduit?

The maximum number of wires in PVC conduit depends on three factors: conduit size, wire gauge, and conduit schedule. For the most common scenario – 12 AWG THHN/THWN in 1/2-inch Schedule 40 PVC – the limit is 8 conductors.

The NEC establishes fill limits in Chapter 9, Table 1:

  • 1 conductor: 53% maximum fill
  • 2 conductors: 31% maximum fill
  • 3 or more conductors: 40% maximum fill

These percentages apply to the conduit’s total internal cross-sectional area. For most installations with three or more wires, you’re working with the 40% rule.

The tables below show maximum conductor counts for common wire gauges and conduit sizes. These numbers assume all conductors are the same type (THHN/THWN) – mixed conductor types require manual calculation.

PVC Conduit Fill Chart – Schedule 40

Schedule 40 PVC is the standard for most electrical installations. The following table shows maximum conductor counts based on NEC Table C10:

Conduit Size14 AWG12 AWG10 AWG8 AWG6 AWG4 AWG
1/2″1185211
3/4″21159532
1″342515864
1-1/4″60432615107
1-1/2″82593620149
2″1359860342415

These values apply to THHN, THWN, and THWN-2 conductors – all three share identical cross-sectional areas. The NEC fill values for these conductor types have remained unchanged since the 2017 edition.

For wire sizes larger than 4 AWG or conduit sizes larger than 2 inches, refer to NEC Table C10 directly.

What Is the 40% Fill Rule and Why Does It Exist?

The 40% fill rule exists for two practical reasons: heat dissipation and wire pulling.

When conductors carry current, they generate heat. Air space around the wires allows that heat to dissipate. Fill a conduit to 100% and the wires overheat, insulation degrades, and fire risk increases.

The second reason is mechanical. Pulling wires through conduit creates friction. At higher fill percentages, wires jam against each other and the conduit walls. The 40% limit ensures conductors can actually be installed without damaging insulation.

Different fill percentages for different conductor counts reflect this reality:

Number of ConductorsMaximum FillReasoning
153%Single conductor can be centered, minimal contact
231%Two conductors create more friction points
3+40%Multiple conductors need space to spiral

I recommend treating 40% as a ceiling, not a target. The NEC permits it, but that doesn’t mean you should design to it. Wire pulling at 40% fill through anything but a straight run with no bends becomes difficult – and sometimes impossible.

Do Ground Wires Count in Conduit Fill Calculations?

Yes. Always. No exceptions.

The NEC states clearly: “Equipment grounding or bonding conductors, where installed, shall be included when calculating conduit or tubing fill.” This applies whether the ground conductor is bare or insulated.

For bare conductors, use NEC Chapter 9, Table 8 to find cross-sectional areas. For insulated ground conductors, use Table 5 – the same table used for circuit conductors.

This rule catches many electricians off guard. The assumption that ground wires “don’t really count” leads to one of the most frequently cited code violations during inspections.

Here’s how this affects a real installation. Consider a residential 20-amp circuit:

  • 3 x 12 AWG THHN conductors (hot, neutral, switched hot)
  • 1 x 10 AWG bare ground

Many electricians would look at the fill chart, see “8 wires maximum for 12 AWG in 1/2-inch conduit,” and assume they’re fine. But the 10 AWG bare ground has an area of 0.0066 square inches. That ground must be counted.

The calculation:

  • 3 x 12 AWG THHN = 3 x 0.0133 = 0.0399 sq in
  • 1 x 10 AWG bare = 0.0066 sq in
  • Total = 0.0465 sq in
  • 1/2″ Schedule 40 internal area = 0.285 sq in
  • Fill percentage = 0.0465 / 0.285 = 16.3%

This particular example passes easily. But add a few more circuits to that same conduit without counting grounds, and you’ll fail inspection.

Schedule 40 vs Schedule 80: Which Should You Use?

Default to Schedule 40 unless the NEC specifically requires Schedule 80.

Both schedules share the same external diameter, which means fittings are interchangeable. The difference is wall thickness. Schedule 80 has thicker walls (0.179 inches vs 0.133 inches for 1-inch conduit), which means a smaller internal diameter – and fewer wires.

Trade SizeSchedule 40 Internal Area (sq in)Schedule 80 Internal Area (sq in)Capacity Reduction
1/2″0.2850.21724% fewer wires
3/4″0.5080.40919% fewer wires
1″0.8320.68817% fewer wires
1-1/4″1.4531.23715% fewer wires
1-1/2″1.9861.71114% fewer wires
2″3.2912.87413% fewer wires

Schedule 80 PVC costs 20-50% more than Schedule 40, depending on manufacturer. You’re paying a premium for thicker walls that actually reduce wire capacity.

The NEC requires Schedule 80 where conduit is “subject to physical damage.” This typically means:

  • Exposed runs below 8 feet in commercial/industrial settings
  • Areas with vehicle traffic
  • Outdoor installations at ground level

For conduit run inside walls, above ceilings, or in other protected locations, Schedule 40 is the correct choice. Over-specifying Schedule 80 wastes money and reduces wire capacity for no benefit.

What Is the 60% Fill Exception for Conduit Nipples?

Conduit nipples 24 inches or less can be filled to 60% instead of 40%.

The NEC states: “Where conduit or tubing nipples having a maximum length not to exceed 24 inches are installed between boxes, cabinets, and similar enclosures, the nipples shall be permitted to be filled to 60% of their total cross-sectional area.”

The 2023 NEC clarified an important detail: the 24-inch measurement does not include connectors. This is the conduit body length only.

This exception exists because short runs don’t create the same wire-pulling difficulties as long runs. There’s no friction buildup over distance, and heat dissipation is less critical over such short lengths.

Practical applications include:

  • Panel-to-panel connections in electrical rooms
  • Stub-ups from floor boxes
  • Short connections between junction boxes

Use this exception deliberately, not as a way to squeeze in one more wire. The 60% fill is still a maximum, and cramming conductors into nipples makes terminations more difficult.

Do You Need to Derate Ampacity for Multiple Conductors?

Yes – and this requirement catches many electricians who focus only on fill calculations.

When more than three current-carrying conductors occupy a conduit, the ampacity of each conductor must be derated according to NEC 310.15(B)(3)(a):

Number of Current-Carrying ConductorsAmpacity Adjustment
4-680% of rated ampacity
7-970% of rated ampacity
10-2050% of rated ampacity
21-3045% of rated ampacity

The key phrase is “current-carrying conductors.” Equipment grounding conductors do NOT count toward this derating calculation – even though they DO count for fill calculations. Neutral conductors that only carry unbalanced current also don’t count.

This creates a common oversight. An electrician calculates conduit fill, confirms compliance with the 40% rule, and installs the conductors. But with 10 circuits sharing a conduit, each wire can only carry 50% of its rated ampacity. The installation passes fill requirements but violates ampacity requirements.

For high-density conduit runs, verify both fill AND ampacity before sizing conductors and conduit.

How to Calculate Conduit Fill Step by Step

When you have mixed wire sizes or need to verify fill manually, use this calculation method:

Step 1: Find conductor areas

Use NEC Chapter 9, Table 5 for insulated conductors. Common THHN/THWN values:

Wire SizeArea (sq in)
14 AWG0.0097
12 AWG0.0133
10 AWG0.0211
8 AWG0.0366
6 AWG0.0507
4 AWG0.0824

Step 2: Find conduit internal area

Use NEC Chapter 9, Table 4 for conduit dimensions:

Trade SizeSchedule 40 (sq in)Schedule 80 (sq in)
1/2″0.2850.217
3/4″0.5080.409
1″0.8320.688
1-1/4″1.4531.237
1-1/2″1.9861.711
2″3.2912.874

Step 3: Calculate fill percentage

Fill % = (Total Conductor Area / Conduit Internal Area) x 100

Step 4: Compare to NEC limits

For three or more conductors, the result must be 40% or less (60% for nipples).

Example calculation:

Installing 4 x 10 AWG THHN + 2 x 12 AWG THHN + 1 x 10 AWG bare ground in 3/4″ Schedule 40 PVC:

  • 4 x 10 AWG THHN = 4 x 0.0211 = 0.0844 sq in
  • 2 x 12 AWG THHN = 2 x 0.0133 = 0.0266 sq in
  • 1 x 10 AWG bare = 0.0066 sq in
  • Total conductor area = 0.1176 sq in
  • 3/4″ Schedule 40 internal area = 0.508 sq in
  • Fill percentage = 0.1176 / 0.508 = 23.1%

This installation complies with NEC fill requirements.

Common Conduit Fill Mistakes That Fail Inspection

Beyond the ground wire issue addressed earlier, several other mistakes lead to failed inspections:

Using plumbing PVC instead of electrical PVC. Plumbing schedule designations (Schedule 40, Schedule 80) use the same names as electrical conduit, but plumbing PVC is not listed for electrical use. The internal dimensions also differ slightly. Use only PVC conduit manufactured and listed for electrical applications.

Forgetting ampacity derating. As covered above, fill compliance does not equal ampacity compliance. Verify both requirements.

Too many bends. The NEC limits total bending to 360 degrees (equivalent to four 90-degree bends) between pull points. Exceeding this makes wire pulling nearly impossible – and even approaching the limit at high fill percentages creates serious installation difficulty.

Filling to the maximum. Just because you CAN fill to 40% doesn’t mean you should. Experienced electricians target 60-70% of the maximum allowable fill (24-28% actual fill). This leaves room for future additions and makes wire pulling substantially easier.

A conduit at 25% fill pulls smoothly. The same conduit at 38% fill becomes a struggle – technically compliant, but practically miserable. Leave yourself margin.

Ready to Plan Your Installation?

Several online calculators can verify your conduit fill calculations:

  • Southwire Conduit Fill Calculator
  • Nassau National Cable Calculator
  • Belden Conduit Fill Calculator

For complex installations with mixed conductor types, multiple conduit runs, or unusual routing requirements, consult with a licensed electrical engineer to ensure both fill and ampacity requirements are met throughout the system.

Newsletter Updates

Enter your email address below and subscribe to our newsletter